Skip to content
de Bekker Solutions 3D world (in Dutch)

Knowledge

Dehumidification with heat recovery: how it works

In a swimming pool, a greenhouse or a drying room, a lot of water ends up in the air every day. That moisture has to go. The only question is: do you throw away the heat contained in that moisture, or do you use it again? This page explains how that works.

Have your situation calculatedBuild your own space in the 3D world (in Dutch)

Why does indoor air become humid?

Water evaporates wherever it gets the chance: from a swimming pool, from wet floors, from the leaves of plants and from products that are drying. That water vapour goes into the air.

Warm air can hold more water vapour than cold air. But even warm air fills up at some point. How full the air is, is given by the relative humidity, as a percentage. At 100% nothing more fits in.

What is latent heat?

Evaporating water takes heat. That heat is then held in the water vapour. You do not feel it as temperature, which is why it is called latent (hidden) heat. For each litre of water, it comes to about 0.68 kWh.

The heat is only released again when the vapour condenses, in other words when it turns back into water. That happens on any surface that is colder than the dew point of the air. On a cold window that is a nuisance. In a heat pump it is exactly what you want.

Sensible and latent heat side by side
Sensible heatLatent heat
What it isheat you measure as temperatureheat held in water vapour
What you noticethe air gets warmer or colderthe air gets more humid or drier
Recovering itwith a heat exchangerby letting the vapour condense, for example on the evaporator of a heat pump

Why ventilating moisture away costs energy

The simplest way to get rid of moisture is to ventilate: humid air out, drier outdoor air in. That works. But the air you blow outside is warm and full of latent heat. And the air that comes in has to be heated again.

A heat exchanger helps. It passes heat from the exhaust air to the fresh air. The Dutch knowledge centre Stimular writes that in a swimming pool, depending on the type of installation, 40 to 80% of the heat can be retained. Such a heat exchanger mainly transfers sensible heat. Part of the latent heat still leaves with the water vapour.

The same applies in a greenhouse. According to research by Wageningen University & Research, dehumidifying by ventilation in a tomato crop easily costs 8 to 10 m³ of natural gas per m² per year.

How a heat pump recovers the moisture and the heat

  1. Humid air flows past the cold evaporator of the heat pump.
  2. The air cools below its dew point. The water vapour condenses and drains away as water.
  3. As it condenses, the latent heat is released. The heat pump takes it up, together with sensible heat from the air.
  4. The heat pump raises the heat to a higher temperature and releases it where you need it: to the dry air, to the pool water or to a process.
Dehumidification with a heat pump Humid, warm air flows past the cold evaporator. The vapour condenses and drains away as condensate. Through the heat pump the heat goes to the condenser, which releases it to the dry air, the pool water or a process. Humid, warm air full of vapour and latent heat Evaporator (cold) the vapour condenses Condensate drains away via the heat pump Condenser (warm) releases the heat again Dry, warm air back into the space, or the heat goes to the pool water or a process
The principle of dehumidification with a heat pump (simplified).

So the moisture disappears and the heat stays inside. What you put in is mainly the electricity for the compressor and the fans. A swimming pool or a greenhouse also always needs some fresh outdoor air. You can recover the heat from that air as well.

How is this different from an ordinary air handling unit?

An air handling unit refreshes, filters and heats or cools air. With an integrated heat pump, the same unit can also actively dehumidify and recover the latent heat. Read more on the page about the air handling unit with an integrated heat pump.

Where is this used?

What the X-Cross does

The X-Cross is our unit for this approach. It recovers heat from air that you have to dehumidify anyway, and it heats, cools and dehumidifies in one unit. We build it together with Wagenaar Refrigeration.

Which unit suits you follows from a calculation using your own figures. The report shows the latent and the sensible load separately, with the standards and the assumptions.

Questions we are often asked

Is dehumidification the same as ventilation?

No. Ventilation refreshes the air and removes moisture along the way. Dehumidification takes the moisture out of the air itself, for example by letting it condense. You often need both: fresh air for people or plants, and dehumidification for the moisture balance.

How much heat is there in the moisture?

Every litre of water that evaporates takes about 0.68 kWh of heat. That heat is then held in the water vapour. If you recover it, you do not have to generate it again.

Does heat pump dehumidification also work in winter?

Yes. The moisture comes from inside: from the water, the crop or the product. The heat pump works with that indoor air. On the X-Cross Blue Line, an evaporator on the roof draws extra heat from the outdoor air in cold weather.

How do I find out what this means for my space?

Do the quick scan in the 3D world for a first indication, or recreate your own space there. The 3D world is in Dutch for now. We make the real calculation using your figures.

Further reading

Sources

Have your situation calculated

Send us a short description of your space, or give us a call. You can also submit a request in the 3D world (in Dutch), after the quick scan.

Email
info@debekkersolutions.nl
Phone
+31 6 22 42 49 58